Standard Maintenance Contract Service List
- Change oil and oil filter, change fuel filter, test coolant & change if necessary with new coolant and filter..
- Service air cleaner, check for restrictions and contaminants
- Check coolant concentration and level- adjust to 50/50 mix
- Inspect cooling system hoses for cracks and distortions, tighten clamps
- Inspect radiator for restrictions and corrosion, check block heater
- Check for coolant, fuel and oil leaks, tighten connections as necessary
- Check belts and pulleys for cracks and wear, adjust as necessary
- Inspect and clean crankcase breather- check for excessive pressure
- Inspect governor and injection pump for leaks and proper operation
- Check turbo charger for proper clearance and freedom of movement
- Inspect ignition system (pts, rotor, plugs etc. for gaseous engines)
- Check air intakes and outlets for contaminants, airflow and restrictions
- Check fuel tank for contaminants and condensation
- Check hoses, piping and connections- check for chafing and restrictions
- Inspect silencer, remove debris and build-up
- Drain exhaust line trap
- Inspect hangars, anchors and supports for exhaust system
- Inspect exhaust for cracks and leaks
- Check battery charge operation and charge rate-adjust as necessary
- Load test battery- Clean terminals and apply protectant
- Check cables and ends
- Visually inspect generator end for signs of heat and wear-check brushes and bearings.
- Visually inspect controls and breakers for signs of heat and wear
- Check mounting bolts/anchors for tightness and stability
- Test run generator. Check all gauges for proper operation
- Check for proper frequency and voltage- adjust as necessary
- Check engine alternator charge rate
- Check for vibration, leakage and noise
- Inspect Transfer Switch connections for signs of heat and wear
- Inspect Transfer Switch with infrared temp gun to check for loose connections
- Transfer building load to generator (if permitted), monitor for proper transfer sequence
- Return Transfer Switch to standby position, monitor for proper shutdown sequence
|