STANDARD MAINTENANCE CONTRACT SERVICE LIST

 

  • Change oil and oil filter, change fuel filter, change coolant filter.
  • Service air cleaner, check for restrictions and contaminants
  • Check coolant concentration and level- adjust to 50/50 mix
  • Inspect cooling system hoses for cracks and distortions, tighten clamps
  • Inspect radiator for restrictions and corrosion, check block heater
  • Check for coolant, fuel and oil leaks, tighten connections as necessary
  • Check belts and pulleys for cracks and wear, adjust as necessary
  • Inspect and clean crankcase breather- check for excessive pressure
  • Inspect governor and injection pump for leaks and proper operation
  • Check turbo charger for proper clearance and freedom of movement
  • Inspect ignition system (pts, rotor, plugs etc. for gaseous engines)
  • Check air intakes and outlets for contaminants, airflow and restrictions
  • Check fuel tank for contaminants and condensation
  • Check hoses, piping and connections- check for chafing and restrictions
  • Inspect silencer, remove debris and build-up
  • Drain exhaust line trap
  • Inspect hangars, anchors and supports for exhaust system
  • Inspect exhaust for cracks and leaks
  • Check battery charge operation and charge rate-adjust as necessary
  • Load test battery- Clean terminals and apply protectant
  • Check cables and ends
  • Visually inspect generator end for signs of heat and wear-check brushes and bearings.
  • Visually inspect controls and breakers for signs of heat and wear
  • Check mounting bolts/anchors for tightness and stability
  • Test run generator. Check all gauges for proper operation
  • Check for proper frequency and voltage- adjust as necessary
  • Check engine alternator charge rate
  • Check for vibration, leakage and noise
  • Inspect Transfer Switch connections for signs of heat and wear
  • Inspect Transfer Switch with infrared temp gun to check for loose connections
  • Transfer building load to generator (if permitted), monitor for proper transfer sequence
  • Return Transfer Switch to standby position, monitor for proper shutdown sequence
 

 